FIRE EXTINGUISHING CONTROL PANEL: FS5200E
Description
FS5200E is already certified by EVPU!!! The Fire Extinguishing Control Panel is designated for fire protection, monitoring and control of systems for active extinguishing – gas, powder, aerosol, water, etc. After processing the signals from the automatic fire detectors and/or manual call points the Control Panel makes commands to the executive devices for extinguishing, sound-light signalers, air conditioning and ventilation devices, etc. The Control Panel could exchange data with a repeater, PC or another intelligent device via RS 485 interfaces. – Control of the lines, the controllable inputs and outputs for Fault condition and automatic resetting – Control of the lines for removed fire detector and automatic resetting – Option for setting the evacuation time from 0 to 5 minutes – Option for setting the time when the extinguishing device is switched on from 10 seconds to 5 minutes – Built-in sounder for Fire condition and Fault condition with the option for switching off – Built-in clock for astronomic time – Test modes and setting option – Power independent archive of 100 events registered by the Control Panel, containing the type, date and time of the event FIRE ALARM LINES: 3 MAXIMUM NUMBER OF FIRE DETECTORS IN A LINE: 32 CONTROLLABLE OUTPUTS RELAY (24±3)V DC: RELAY OUTPUTS SWITCHING 3À/125V AC, 3A/30V DC: OUTPUTS OPEN COLLECTOR TYPE: 3 SIGNALIZATION OF REGISTERED EVENTS: POWER SUPPLY: MAXIMUM CURRENT TO EXTERNAL DEVICES: 2,5 A at (24±3)V DCPRODUCT DESCRIPTION
Functional data
Technical data
– with extinguishing control: 2
– without extinguishing control: 1
CONTROLLABLE INPUTS FOR:
– manual extinguishing activation: 1
– extinguishing keeping: 1
– extinguishing disable: 1
– mode selection: 1
– monitoring the extinguisher outflow: 1
– for sounders in Fire condition: 1
-for sounders in Extinguishing status: 1
-for Extinguishing switching on: 1
– for Fire condition: 3
– for Extinguishing: 3
– for Fault condition: 3
– sound: built-in sounder
– light: LED
– text messages: LCD display, backlit
– mains: 220/230V AC, 50/60 Hz
– backup battery: 2x12V DC, 12 Ah
OPERATING TEMPERATURE: minus 5oC to 40oC
RELATIVE HUMIDITY: (93±3)% at 40oC
DIMENSIONS: 450x355x115 mm
WEIGHT (EXCLUDING THE BACKUP BATTERY): 6,6 kg