• Company
  • Products
  • Catalogues
  • News and Trends
  • Events
  • Projects
  • Jobs
  • Properties
new

PVC Insulation TYPE A (IEC 60502-1), PVC Insulation TYPE TI1(BS EN 50363)

Add to My Constguide favorites
PVC Insulation TYPE A (IEC 60502-1), PVC Insulation TYPE TI1(BS EN 50363) PVC Insulation TYPE A (IEC 60502-1), PVC Insulation TYPE TI1(BS EN 50363)

Description

LV CABLES

Low Voltage Cables are used to supply power to large motors and industrial equipment in both residential and industrial settings.

At Riyadh Cables, we produce Low Voltage Cables in both PVC and XLPE insulations of copper and aluminium, with armoured and un-armoured designs, and in single or multi-core constructions.

The performance and load specifications of PVC and XLPE insulated cables determine the specific use of Low Voltage Cables. PVC insulated Low Voltage Cables may be used for electrical power, lighting and wiring for residential and administrative office buildings. XLPE insulated Low Voltage Cables are ideally suited to industrial applications, with an operating temperature of 90⁰C. Our Low Voltage Cables are manufactured to IEC 60502-1 specifications.

In addition to the regular range of Low Voltage Cables, we are also able to supply Low Voltage Cables with special flame retardant PVC Outer Sheathing to comply with the flame retardant test requirements outlined in IEC 60332-1, IEC 60332-3-22, IEC 60332-3-23 or IEC 60332-3-24. We can also manufacture cables with low smoke halogen free (LSHF) material (type ST8) as per IEC 60502-1.

LV CABLES TYPES

PVC INSULATION STANDARD : IEC 60502-1, BS EN 50363

 

PARTICULARS & GUARANTEES RELATING TO PVC INSULATING COMPOUND (TYPE A)
Sl. No.
Description
Unit
Guaranteed Particulars
 1
Tensile Strength and Elongation at break:
 
Min Tensile strength
 N/mm²
 12.5
 
Min elongation at break
 %
 150
 2
Low temperature bend test:
 
Temperature at which specimen shall not crack
 °C
 -15±2
 3
Low temperature elongation test:
 
Test temperature
 °C
 -15±2
 
Min. Elongation
 %
 20
 4
Low temperature Impact test:
 
Test temperature
 °C
 -
 
Min. Elongation
 
 
 5
Accelerated ageing for specified at specified temperature followed by loss of mass test:
 
Max. loss of mass after ageing 7 days at 80 ± 2 °C
 mg/cm²
 -
 6
Accelerated ageing for specified period specified temperature followed by tensile strength & elongation at break
 
Number of Days ageing
 Days
 7
 
Ageing Temperature
 °C
 100 ± 2
 
Tensile Strength after ageing:
 
 
 
Min. value
 N/mm²
 12.5
 
Max. variation
 %
 25
 
Elongation at break after ageing:
 
 
 
Min. value
 %
 150
 
Max. variation from unaged value
 %
 25
 7
Pressure test at high temperature:
 
Test temperature
 °C
 80 ± 2
 
Max. indentation
 %
 50
 8
Resistance to cracking
 
Temperature at which specimen shall not crack
 °C
 150 ± 2
 9
Insulation resistance constant:
 
Min. K. value at 70°C
 M.Ohm.km
PVC Insulation TYPE A (IEC 60502-1), PVC Insulation TYPE TI1(BS EN 50363)

 

Other Riyadh Cables Group products

Similar_Products

\