CONVENTIONAL FIRE CONTROL PANEL: FS4000/2
Description
Fire control panel FS4000 is designed to operate with conventional automatic fire detectors and manual call points. The panel has outputs provided for external executive devices. The unit is produced in four versions: Fire alarm lines: Current thresholds for: Monitored outputs for fire condition: Relay outputs for fire condition: Relay output for fault condition: Relay output for fault condition: Indications of registered events: Power supply: Backup batteries: Operation in Duty mode upon interruption in main power supply: Consumption on backup batteries supply: Power supply to external devices: Fuses: Dimension: 304mm x 222mm x 94mmPRODUCT DESCRIPTION
2 fire alarm lines – FS4000/2
4 fire alarm lines – FS4000/4
6 fire alarm lines – FS4000/6
8 fire alarm lines – FS4000/8Technical features
– Maximum number of fire detectors in a line: 32
– Connecting line: two-wire
– Maximum resistance of a line: 100 Ω
– Fault condition: 0 – 6 mA
– Duty mode: 6 – 16 mA
– Fire condition: 16 – 80 mA
– Short circuit: > 80 mA
– Number: 2 pcs
– Type: potential, relay with independent control
– Electrical characteristics: (19-27.5)V DC/1A
– Number: 2 pcs
– Type: potential-free,1 switching, 1 NO
– Electrical characteristics: 3А/125V AC, 3A/30V DC
– Number: 1 pcs
– Type: potential-free, switching
– Electrical characteristics: 3А/125V AC, 3A/30V DC
– Number: 1 pcs
– Type: none-monitored type activated on short-circuit (from potential free contact)
– Electrical characteristics: 5 VDC on normal open state / 0 VDC in activation mode
Performance:
– Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
– Detection of removed fire detector and automatic reset.
– Identification of manual call points.
– LED indication for alarm state and emergency.
– Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6 or 7 minutes after fire condition is registered.
– Option for ‘LOGICAL AND’ realization of two fire alarm lines.
– Duty Mode condition with direct activation of Fire Condition 2nd Stage ” for two fire alarm lines.
– Status Indication of the device for data transmission RS485.
– Option for switching on/off interface RS485 communication.
– Built-in sounder for fire condition – one tonal, continuous, can be switched off.
– Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
– Test mode for fire alarm lines.
– Disabling fire alarm lines.
– Disabling outputs for fire condition.
– Expanding the options by means of extra relay outputs for fire condition for each line and built-in RS485 for operation in a local network.
– Input for remote Reset fires operation;
– Light indication: LED
– Sound: Built-in buzzer
– Voltage: (100-240)V AC
– Frequency: 50/60 Hz
– Battery type: lead, gel electrolyte
– Number of batteries: 2 pcs
– Nominal voltage of the backup battery: 12V
– Nominal capacity C20: (7,0) Ah
– Charge voltage: 28V DC
Lines – 24V / 1,2Ah – 24V / 4,5Ah – 24V / 7,0Ah
2 lines – 32 h – 120 h – 180 h
4 lines – 24 h – 98 h – 140 h
6 lines – 20 h – 80 h – 110 h
8 lines – 16 h – 68 h – 90 h
– Configuration of 2 lines: < 35 mA at 24V DC
– Configuration of 4 lines: < 45 mA at 24V DC
– Configuration of 6 lines: < 55 mA at 24V DC
– Configuration of 8 lines: < 65 mA at 24V DC
– Voltage: (19-27)V DC
– Maximum current value (including current of contr.outputs): 1,2A
– Main supply 230V: 4.0 A
– Backup battery: 6.0 A
– Power supply to external devices: 1.85 A automatic
– Monitored outputs: 1.1 A automatic
Weight (backup batteries not included): 0.98 kg