CONVENTIONAL FIRE CONTROL PANEL: FS5200/8
Description
FS5200 is already certified by EVPU!!! FIRE ALARM LINES CONTROLLABLE OUTPUTS RELAY OUTPUTS FOR FAULT CONDITIONS RELAY OUTPUTS FOR FAULT CONDITIONS INDICATIONS OF REGISTERED EVENTS ACCESS LEVELS TO CONTROL FUNCTIONS: 4 (in compliance with EN 54/2) POWER SUPPLY BACKUP BATTERIES: 2x12V / 12 Ah OPERATION IN DUTY MODE UPON INTERRUPTED MAINS SUPPLY CONSUMPTION ON BACKUP BATTERIES SUPPLY IN DUTY MODE AT 24 V POWER SUPPLY TO EXTERNAL DEVICES WEIGHT (BACKUP BATTERIES NOT INCLUDED): 6,6 kg FS 5200 FS 5200 + 5201 FS 5200+5201+5202 FS 5200+5201+5202+5201 In each one configuration it is possible to add just one module 5203 or 5204PRODUCT DESCRIPTION
– Maximum number of fire detectors in a line: 32
– Connecting line: two-wire
– Maximum resistance of a line: 100Ω
– Type: Potential
– Electrical characteristics: (24±5)V/500 mA
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC; 3 A/30 V DC
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC; 3 A/30 V DC
– Light indication: LEDs
– Text messages: LCD display – 4 lines, 20 symbols, Latin/Cyrillic characters, backlit
– Sound: Built-in sounder
– Voltage: 220/230 V
– Frequency: 50 Hz
– Minimum configuration: 80 h
– Maximum configuration 30 h
– Minimum configuration: <155 mA
– Maximum configuration: <400 mA
– Voltage: (24±5)V
– Maximum current value (current of controllable outputs included): 1,5 A
DIMENSIONS: 450 x 355 x 115mm
OPERATING TEMPERATURE: -5 oC to +40 oC
RELATIVE HUMIDITY: to 93 %
DEGREE OF PROTECTION: IP 40Possible configurations:
– 8 fire alarm lines
– 1 controllable output
– 2 relay outputs for fire
– 16 fire alarm lines
– 1 controllable output
– 2 relay outputs for fire
– 24 fire alarm lines
– 2 controllable outputs
– 2 relay outputs for fire
– 32 fire alarm lines
– 2 controllable outputs
– 2 relay outputs for fire